Thursday, April 14, 2011

FEPC Update to Information Sheet Regarding the Tohoku Earthquake 4/14

Update to Information Sheet Regarding the Tohoku Earthquake
The Federation of Electric Power Companies of Japan (FEPC) Washington DC Office
As of 12:00PM (EST), April 14, 2011

For your reference, JAIF (Japan Atomic Industrial Forum) has been posting the translation of news reports on their website.

  • Radiation Levels
    • On April 13, TEPCO announced the result of the analysis of water samples from the spent fuel pool at Unit 4 of Fukushima Daiichi Nuclear Power Plant taken on April 12. The concentration of radioactive nuclides were as follows:
    • TEPCO also announced the temperature of the pool water was approximately 194 degrees Fahrenheit when the samples were taken.

Nuclides
(half-life)
Concentration (Unit : Bq/cm3)
Sampled on April 12
Sampled on March 4
I-131
(8 days)
2.2 x 102
Under the Detection Limit
Cs-134
(2 years)
8.8 x 101
Under the Detection Limit
Cs-137
(30 years)
9.3 x 101
1.3 x 10-1

    • The concentration of radioactive nuclides from the seawater sampled at the screen device (installed to remove waste before the intake of seawater) of Unit 2 and sampled near the seawater discharge point (south side) of Fukushima Daiichi Nuclear Station were as follows:

Nuclides
(half-life)
Concentration (Unit : Bq/cm3)
Ratio
Sampled at the screen of Unit 2 at 8:25AM on April 13  (a)
Sampled at south side discharge point at 2:00PM on April 13  (b)
Maximum Permissible Water Concentration (c)
a / c
b / c
I-131
(8 days)
1.0 x 102
9.7 x 10-1
4.0 x 10-2
2,500
24
Cs-134
(2 years)
5.5 x 101
1.4 x 100
6.0 x 10-2
920
23
Cs-137
(30 years)
5.5 x 101
1.4 x 100
9.0 x 10-2
610
16

    • At 8:00PM (JST) on April 14, radiation level at main gate (approximately 3,281 feet from Unit 2 reactor building) of Fukushima Daiichi Nuclear Power Station: 71 micro Sv/hour.
    • At 8:00PM on April 14, radiation level at west gate (approximately 3,609 feet from Unit 2 reactor building) of Fukushima Daiichi Nuclear Power Station: 36.8 micro Sv/hour.
    • Measurement results of environmental radioactivity level around Fukushima Nuclear Power Station announced at 7:00PM on April 14 are shown in the attached PDF file. English version is available at:    http://www.mext.go.jp/english/radioactivity_level/detail/1304082.htm
    • For comparison, a human receives 2,400 micro Sv per year from natural radiation in the form of sunlight, radon, and other sources. One chest CT scan generates 6,900 micro Sv per scan.

  • Plant Parameters

Unit 1
Unit 2
Unit 3
Unit 4
Unit 5
Unit 6
pressure inside the reactor core (gauge pressure, MPa)
0.423
-0.016
-0.017
-
0.003
0.010
4/14
12:00PM
4/14
12:00PM
4/14
12:00PM
-
4/14
8:00AM
4/14
8:00AM
pressure inside the primary containment vessel (absolute pressure, MPaabs)
0.190
0.090
0.1040
-
-
-
4/14
12:00PM
4/14
12:00PM
4/14
12:00PM
-
-
-
water level inside the reactor core (meter) *1
-1.6
-1.5
-1.8
-
+1.842
+2.268
4/14
12:00PM
4/14
12:00PM
4/14
12:00PM
-
4/14
8:00AM
4/14
8:00AM
temperature of the reactor vessel measured at the water supply nozzle (degrees Fahrenheit)
392.5
...

[Message clipped]  View entire message